Plastic insulated prefabricated branch cable
Key words:
Classification:
- Product Description
-
- Commodity name: Plastic insulated prefabricated branch cable
- Commodity ID: 1171377231507378176
Product overview
Pre-branch cable is a complete and continuous set of cables prefabricated by the factory. At the specified position and requirements of the trunk cable, the conductors of the trunk cable and the branch cable are compressed and connected by copper or copper alloy pipe, and complete insulation treatment is carried out. Ensure that the cable tap is safe for electricity, with suitable lifting devices at the upper end for vertical laying, and optional traction members for horizontal laying.Scope of application
Prefabricated branch cables can be widely used in residential, office buildings, hotels, hospitals, shopping malls, factories and other power distribution systems.Executive standard
This product implements JG/T 147-2002 "Rated Voltage 0.6/1kV Copper Core Plastic Insulated Prefabricated Branch Power Cable" and JB/T 10636-2006 "Rated Electrical 0.6/1kV(Um = 1.2KV) Copper Core Plastic Insulated Prefabricated Branch Power Cable".Use Features
1. The maximum working temperature of conductor: cross-linked polyethylene insulation is 90 ℃; PVC insulation is 70 ℃.
2. When short circuit (the longest duration is not more than 5s), the maximum working temperature of cable conductor: XLPE insulation is not more than 250 ℃; PVC insulation is not more than 160 ℃.
3. The ambient temperature during cable laying shall not exceed 0 ℃.
4. The rated voltage U0/U(Um) of the cable is 0.6/1(1.2)kV.
U0: Rated power frequency voltage between conductor to ground or metal shield for cable design;
U: Rated power frequency voltage between conductors for cable design;
Um: The maximum value of the "maximum system voltage" that the device can withstand.
5. The allowable bending radius shall not exceed 30 times of the outer diameter of the cable;Test voltage
Cable water test voltage is 3.5kV,5min insulation does not occur breakdown.Type of cable
Model
Name
FZVV
FZYJV
-FZVV
Za -FZYJV
WDZA-FZIONS
Nb-FZYJVCopper conductor PVC insulated PVC sheathed prefabricated branch cable
Copper conductor XLPE insulated PVC sheathed prefabricated branch cable
Copper conductor PVC insulated PVC sheathed flame retardant prefabricated branch cable
Copper conductor XLPE insulated PVC sheathed flame retardant prefabricated branch cable
Copper conductor XLPE insulated low smoke free flame retardant polyolefin sheathed prefabricated branch cable
Copper conductor XLPE insulated PVC sheathed fire-resistant precast branch cablea If the requirements of Class A, Class B and Class C in GB/T 18380.3 are met, the codes are ZA, ZB and ZC respectively; The code for meeting the requirements of Class D in IEC60332 is ZD.
B Code NA and NB for those meeting Class A and Class B requirements in GB/T 19216.21.Cable specifications
Model
Number of cores
Nominal cross-sectional area mm2
Backbone cable
Branch cable
FZVV、FZYJV
FZVV
FZYJV
WDZA-FZIONS1
2
3
4
516~630
16~50
16~50
16~50
16~504~240
4~35
4~35
4~35
4~35Note: The cross-sectional area of the branch cable shall be configured according to the user's requirements, but the cross-sectional area of the branch cable shall not be greater than the cross-sectional area of the main cable.
The main advantages of prefabricated branch cables
1. It has excellent power supply reliability; 2. It significantly reduces power supply costs; 3. It has excellent shock resistance, air tightness and water resistance.Structure diagram of prefabricated branch cable